Zone 8 Floor (Over Unconditioned Space) Insulation — R-25

The DOE recommends R-25 insulation for the floor (over unconditioned space) in Climate Zone 8 (Subarctic). The typical floor (over unconditioned space) cavity depth is 9.25 inches. This page compares all insulation types showing the thickness needed, material cost per square foot, and whether each type fits within the standard cavity depth.

Quick Summary

Required R-Value
R-25
Cavity Depth
9.25"
Cheapest Option
$3.00/sq ft
Fiberglass Batt
Thinnest Option
5"
Extruded Polystyrene (XPS)

Insulation Type Comparison for Zone 8 Floor (Over Unconditioned Space)

The following table compares all insulation types for achieving R-25 in the floor (over unconditioned space) of a building in Climate Zone 8. Types marked as "recommended" are specifically suited for this building component. The cost estimates represent material costs only and do not include labor, which can add 30-100% depending on the insulation type and project complexity.

Insulation Type R/Inch Thickness Cost/SqFt Cost/1000 SqFt Fits Cavity Recommended
Fiberglass Batt R-3.2 7.8" $3.00 $3,000 Yes Yes
Expanded Polystyrene (EPS) R-3.9 6.4" $3.00 $3,000 Yes Yes
Mineral Wool Batt R-3.3 7.6" $3.75 $3,750 Yes Yes
Extruded Polystyrene (XPS) R-5 5" $4.50 $4,500 Yes Yes
Cotton Denim (Recycled) R-3.5 7.1" $5.00 $5,000 Yes Yes
Blown-In Cellulose R-3.5 7.1" $1.75 $1,750 Yes -
Blown-In Fiberglass R-2.5 10" $2.00 $2,000 No -
Vermiculite (Loose Fill) R-2.1 11.9" $2.50 $2,500 No -
Polyisocyanurate (Polyiso) R-6 4.2" $5.50 $5,500 Yes -
Mineral Wool Board R-4.3 5.8" $6.25 $6,250 Yes -
Sheep Wool R-3.5 7.1" $8.75 $8,750 Yes -
Open-Cell Spray Foam R-3.7 6.8" $10.00 $10,000 Yes -
Closed-Cell Spray Foam R-6.5 3.8" $20.00 $20,000 Yes -
Aerogel Blanket R-10 2.5" $75.00 $75,000 Yes -

Installation Guidance

Floor insulation at R-25 in Zone 8 is installed between floor joists above unconditioned spaces such as garages, crawlspaces, and cantilevers. Standard 2x10 joists provide 9.25 inches of cavity depth, and 2x12 joists provide 11.25 inches. Fiberglass or mineral wool batts are the most common materials, installed with the vapor retarder (if faced) facing upward toward the heated space. The insulation must be in firm contact with the subfloor above — sagging insulation creates an air gap that significantly reduces thermal performance. Support the batts from below using wire stays (tiger claws), netting, or rigid board insulation. In cold climates, supplement batt insulation with a continuous air barrier on the underside to prevent cold air from washing through the insulation. For crawlspace applications in Zone 8, consider converting to an unvented conditioned crawlspace with wall insulation instead of floor insulation for better overall performance.

Construction Notes

Floor insulation is installed between floor joists above unconditioned spaces such as garages, crawlspaces, and cantilevers. Standard floor joists are 2x10 (9.25-inch depth) or 2x12 (11.25-inch depth), providing ample space for batt or blown insulation. The insulation must be in contact with the subfloor above and supported from below, typically with wire stays, netting, or rigid boards. In cold climates, a continuous air barrier on the bottom of the insulation helps prevent cold air washing through the insulation. For floors over unconditioned garages, fire-rated drywall is also required on the garage ceiling per building code, which provides incidental support for the insulation.

Other Components in Zone 8

Floor (Over Unconditioned Space) Requirements in Other Zones